Black Friday10% off the whole site with code BLACKFRIDAY10 · until 30 November

🚚 Free shipping → Free delivery throughout Italy! (excluding remote areas and smaller islands)

🚪 Order on WhatsApp! → Can't find the door you're looking for? Contact us now!

Designing fire compartmentation in hotels: vertical and horizontal technical solutions according to current regulations

Progettare la compartimentazione antincendio negli hotel: soluzioni tecniche verticali e orizzontali secondo le normative vig

Fire compartmentation is one of the most important elements in hotel safety design, ensuring the protection of occupants and limiting damage in the event of a fire. Compartmentation, as part of passive protection, is based on the use of fire-resistant barriers, such as walls, ceilings and fire doors, which divide the building into compartments. This system is essential to contain fire and smoke in limited areas, allowing the safe evacuation of occupants and facilitating the intervention of firefighters.

Reference legislation: D.M. 9 April 1994 or the Fire Prevention Code

For hotels with more than 25 beds, which are activities subject to inspection by the Italian Fire Brigade (Vigili del Fuoco) under DPR 151/2011, you can follow the traditional technical rule (Ministerial Decree (D.M.) of 9 April 1994) or, as an alternative, the Fire Prevention Code with Chapter S.3 and technical rule V.5: once a route is chosen, it must be followed in full. The Code defines three levels of performance:

- Level I: No requirements (not admissible in subject activities).

- Level II: Limitation of the spread of fire within the same activity or towards other activities.

- Level III: Limitation of the spread of fire and cold smoke, required for activities with high crowding, complex geometry or high fire load.

Fire resistance classes

The construction elements used for fire compartmentation must have a specific fire resistance class, which is measured according to three parameters:

- R (carrying capacity),

- E (integrity against flames and hot gases),

- I (thermal insulation).

Fire resistance classes are indicated with acronyms such as EI 30, EI 60, EI 120, where the number represents the time in minutes during which the element retains its properties.

Vertical and horizontal compartmentalization in hotels

Vertical compartments

Vertical compartmentalization refers to the separation between the different floors of a building, preventing the spread of fire from the bottom to the top, in accordance with the natural movement of smoke and heat. In hotels, this type of compartmentalization is crucial to protect vertical escape routes, such as stairs and elevators, and prevent the spread of fire from one floor to another.

Practical examples of vertical compartmentalization

  1. Compartmented emergency stairs

Emergency stairs, used to evacuate guests in the event of a fire, are separated from the corridors on each floor by fire doors of the class required for the stairwell, which depends on the height of the building and on the technical rule applied. This way, even in the event of a fire, the stairs remain usable.

  1. Separate elevator shafts

Elevators are critical points for fire safety. If the elevator shaft is not inside a protected staircase, it must be of the protected type: the characteristics of its closures are set by the fire safety design.

  1. Chimneys and ventilation ducts

Chimneys and ventilation ducts must be vertically compartmentalized by fire dampers that close automatically in the event of a fire, to prevent flames and fumes from spreading between floors.

  1. Sections of compartmentalized service stairs

The service stairs, used by staff, are compartmentalized from the areas reserved for guests, to ensure safety even in these alternative escape routes.

  1. Separation between basements and living areas

The technical rooms, garages and warehouses in the basement floors must be compartmentalised from the living areas with fire-resistant elements of the class required by the design, to prevent a fire from spreading to the rooms.

Horizontal compartments

Horizontal compartmentalization refers to the separation of spaces on the same floor, such as corridors, bedrooms, kitchens and common areas. This type of compartmentalization is essential to protect horizontal escape routes and prevent a fire from spreading across an entire floor.

Practical examples of horizontal compartmentalization

  1. Corridors separated from rooms by fire doors

The corridors are compartmentalised horizontally with respect to the rooms: under the traditional technical rule (Ministerial Decree (D.M.) of 9 April 1994), room doors must be at least RE 30 with self-closing in new buildings (RE 15 in existing ones); under the Code, the performance is set by the design. The aim is to prevent the spread of fire along the floor and to protect the escape routes.

  1. Separation between restaurants and rooms

Restaurants, often located on the ground floor or in common areas, are separated from the rooms by fire-resistant floor slabs and walls of the class required by the design, to prevent the spread of fire towards residential areas.

  1. Fire walls between technical and residential areas

The kitchens, laundries and technical areas are separated from the bedrooms and common areas by fire-resistant walls of the class required by the design, to prevent accidental fires from spreading.

  1. Fire barriers between hotel sections

In large hotels, the different sections of the building (wings or blocks) can be separated by fire walls of the class required by the design, to prevent a fire from spreading between different areas.

  1. Compartmentalization of ceilings between common areas and rooms

Floor slabs between common areas, such as conference rooms or restaurants, and guest rooms must be compartmentalized with fire-resistant elements of the class required by the design, so that rooms remain safe in the event of a fire in public areas.

Determination of separation distances

Separation distance is another essential element in fire design, determined to prevent the spread of flames between adjacent compartments or towards other activities. This distance can be calculated with tabular or analytical methods, according to the Fire Prevention Code.

Calculating the separation distance (tabular method)

The formula for calculating the separation distance according to the tabular method is as follows:

Calculation of thermal radiation (analytical method)

The analytical method is based on the calculation of the thermal radiation emitted by a fire. The formula used is the following:

Conclusions

Fire compartmentation, both vertical and horizontal, is an essential component in the passive protection of hotels. The correct design and implementation of fire-resistant compartments, combined with the use of alarm systems and precisely calculated separation distances, ensures the safety of occupants and the protection of facilities. Compliance with the regulations of the Fire Prevention Code and the use of certified materials offer effective protection against the spread of fire, allowing for safe evacuation and facilitating the intervention of rescuers.

FAQ on fire compartmentation in hotels

  1. What is fire compartmentation?

Fire compartmentation is a passive protection technique that involves dividing a building into fire-resistant compartments. These compartments prevent the spread of flames and smoke, limiting damage and ensuring safe escape in the event of a fire.

  1. What are the advantages of compartmentalization in hotels?

Compartmentalization limits the spread of fire, protecting escape routes and allowing guests and staff to evacuate safely. It also reduces structural damage by protecting areas not affected by the fire.

  1. What regulations govern fire compartmentation in Italy?

For hotels, the traditional technical rule (Ministerial Decree (D.M.) of 9 April 1994) applies or, as an alternative, the Fire Prevention Code: Chapter S.3 establishes the criteria for the division into compartments, the fire resistance classes and the separation distances, and technical rule V.5 the specific measures for accommodation facilities.

  1. What is a fire resistance class?

The fire resistance class indicates for how long a building element maintains its performance during a fire. The classes are expressed in minutes, such as EI 30, EI 60 or EI 120: E is integrity against flames and hot gases, I is thermal insulation. Cold smoke tightness is a separate performance (Sa class).

  1. What is the difference between vertical and horizontal compartmentalization?

Vertical compartmentalization separates different floors of a building, while horizontal compartmentalization divides areas within the same floor. Both are essential to prevent the spread of fire in different directions.

  1. What elements need to be compartmentalized in a hotel?

In a hotel, the fire safety design normally compartmentalizes the stairs, the corridors and escape routes, the bedrooms, the kitchens and risk areas, the conference rooms, the elevator shafts and the ventilation ducts.

  1. What is the fire resistance class required for fire doors in hotels?

The class is set by the fire safety design according to the Ministerial Decree (D.M.) of 9 April 1994 or technical rule V.5 of the Code. For example, under the 1994 decree, room doors are at least RE 30, storage room doors REI 60 or REI 90 depending on the floor area, and stair doors follow the class of the stairwell, which depends on the height of the building.

  1. How is the separation distance between compartments determined?

The separation distance can be calculated using tabular or analytical methods provided by the Fire Prevention Code. These methods consider the percentage of perforation of the facades and the thermal radiation emitted by the fire.

  1. What formulas are used to calculate the separation distance?

One of the most common formulas for the tabular method is:

  1. What is the function of fire dampers in ventilation ducts?

Fire dampers automatically close ventilation ducts in the event of a fire, preventing fire and smoke from spreading through the ventilation system between floors of the building.

  1. Why is it important to compartmentalize emergency stairs?

Fire escapes are critical escape routes in the event of a fire. Compartmentalization protects these areas with fire-resistant barriers to prevent flames and smoke from blocking evacuation.

  1. What does the acronym EI 120 mean?

The acronym EI 120 indicates that an element has a fire resistance of 120 minutes, during which it maintains the ability to prevent the passage of flames (E) and the transfer of heat (I).

  1. What are the risks of an inadequate compartmentalization system?

A non-compliant compartmentation system increases the risk of fire spreading rapidly, making evacuation difficult or impossible and causing further damage to the structure.

  1. How are elevators protected during a fire?

If the elevator shaft is not inside a protected staircase, it must be of the protected type, because it is a very vulnerable vertical path for smoke and fire: its characteristics are set by the fire safety design.

  1. What materials are used for compartmentalization barriers?

Materials used for compartmentalization barriers include concrete, fire-resistant brick, fire-resistant plasterboard, and steel. These materials are designed to withstand high temperatures and prevent the spread of fire.

  1. What role do escape routes play in compartmentalization solutions?

Escape routes must be protected and compartmentalized so that they remain safe and accessible during a fire. Fire doors and heavy-duty barriers ensure that they are not blocked by smoke or flame.

  1. How do you prevent fire from spreading through ceilings?

Floor slabs must be compartmented with fire-resistant elements of the class required by the design, which prevent fire from passing from one floor to another through ducts or structures.

  1. What is meant by compartment continuity?

Compartment continuity means that fire barriers must be continuous and uninterrupted, covering all separating surfaces between compartments, including walls, ceilings, and floors.

  1. Should escape routes always be compartmentalized?

As a rule, yes: stairways and corridors must remain protected from fire and smoke for the whole evacuation time; how to compartmentalize them and with which class is set by the technical rule applied (D.M. 9 April 1994 or the Code). This is essential for the safe evacuation of occupants.

  1. What are the complementary technologies to fire compartmentation?

In addition to physical barriers, complementary technologies include fire detection systems, automatic sprinklers, fire dampers and evacuation alarm systems, which together reduce risks and improve the effectiveness of compartmentation.

  1. What are fire doors?

Fire doors are safety devices designed to resist flames and heat during a fire. They are made of fire-resistant materials and have gaskets that expand with heat to seal any gaps, preventing the passage of smoke and flames.

  1. What are the fire resistance classes of fire doors?

Fire doors are classified according to their ability to resist fire and are indicated with acronyms such as EI 30, EI 60, EI 120, where the number represents the minutes of fire resistance. For example, an EI 60 door can resist for 60 minutes before fire damages it.

  1. Where should fire doors be installed in hotels?

Fire doors must be installed in escape routes, such as emergency stairs and corridors, and in areas separating high-risk areas, such as kitchens, from residential compartments (guest rooms).

  1. Do fire doors have to close automatically?

Yes, fire doors must be equipped with self-closing devices to ensure that they close automatically in the event of a fire. In many cases, these doors are held open by an electromagnetic system, which is deactivated in the event of a fire alarm, closing the door.

  1. Do fire doors require maintenance?

Yes, it is essential to carry out regular maintenance of fire doors, checking their integrity, the functioning of the self-closing devices and the intumescent seals, to ensure that they are always operational in the event of an emergency.

Examples of Compartmentalization in Hotels: Doors and Corridors

  1. Fire doors between rooms and corridors

Under the traditional technical rule (Ministerial Decree (D.M.) of 9 April 1994), room doors onto corridors must be at least RE 30 with self-closing in new buildings (RE 15 in existing ones); under the Code (technical rule V.5), the performance is set by the design. Many designers nonetheless choose EI 30 or EI 60 doors.

  1. Intermediate doors in long corridors

In long corridors the designer may provide intermediate fire doors, usually held open by electromagnets, to limit the length of the sections exposed to smoke: however, the Code does not prescribe any fixed distance.

  1. Separation of corridors by automatic fire doors

Automatic fire doors in corridors, held open by electromagnetic devices, close automatically in the event of a fire. This system allows free circulation in normal conditions, but ensures compartmentalization of corridors in an emergency.

  1. Self-closing fire doors in escape routes

Fire doors installed in escape routes (corridors leading to emergency stairs) must be equipped with self-closing devices to ensure that they close in the event of a fire, blocking the spread of fire and smoke towards the stairs.

  1. Compartmentalizing corridors by groups of rooms: what the Code says

According to the Fire Prevention Code, there is no specific requirement that corridors be compartmentalized into sections serving groups of 5-10 rooms each. Compartmentalization in hotels depends on several factors, including:

- Maximum compartment surface area: The regulation establishes limits on the maximum surface area of ​​fire compartments, which vary according to the height of the floors and the Rvita risk profile associated with the occupants. Hotels fall under profile Ciii (occupants who may be asleep, in a managed short-stay activity), and the values are given in the table in Chapter S.3 of the Code.

- Length of escape routes: The maximum length of escape routes is set by the chosen technical rule, and it can increase where there are active protection measures such as sprinkler systems.

- Building configuration and crowding: The design must consider the layout of the spaces, the number of occupants and the available escape routes.

Dividing corridors into sections that serve groups of 5-10 rooms each can be a good design practice to improve fire safety, but it is not a specific regulatory requirement. This choice can help limit the spread of smoke and flame in the event of a fire, but must be evaluated on a case-by-case basis by a qualified professional based on the characteristics of the building.

  1. Double fire doors in main corridors

In main corridors, especially if very long, double fire doors (EI 60) can be installed, which close on both sides of the corridor in the event of a fire alarm, blocking fire and smoke.

  1. Compartmentalized corridors with separation of public areas

Corridors leading to guest rooms are separated from public areas, such as lobbies or restaurants, by fire doors of the class required by the design, to prevent fire from easily spreading to residential areas.

  1. Fire doors for separating hotel wings

In large hotels with multiple wings or sections, corridors can be compartmentalized with fire doors of the class required by the design, to prevent fire from spreading from one wing to another.

  1. Installation of fire-rated glass doors in corridors

In some hotels, glazed fire doors in corridors, with EI 60 fire-resistant glass, can be used to maintain visibility and natural light, while ensuring fire compartmentation.

  1. Compartmentalization between corridors and technical areas

Corridors are separated from technical areas (e.g. boiler rooms or electrical rooms) by fire doors of the class required by the design, so that a fire in the technical areas does not spread to the corridors or rooms.

  1. Fire doors in corridors leading to warehouses

Corridors leading to warehouses are separated by fire doors of the class required by the design (under the Ministerial Decree (D.M.) of 9 April 1994, for example, REI 60 for storage rooms up to 12 m² and REI 90 up to 500 m²), because warehouses may contain combustible materials.

  1. Fire doors in escape routes of corridors that connect to emergency stairs

Doors separating corridors from emergency stairs have the class required for the stairwell and must close automatically in the event of fire, to prevent fire from reaching the stairs and blocking evacuation.

  1. Sliding fire doors in corridors

In some hotels, sliding fire doors may be used in the hallways, which close in the event of a fire. These doors are useful when space is limited and swing doors would be cumbersome.

  1. Compartmentalized corridors to separate the floors

Corridors near the stairs are separated by fire doors of the class required by the design, to prevent the fire from easily spreading between the floors.

  1. Smoke-resistant fire doors in corridors

Where the design requires cold smoke control (Sa class), the doors must also have cold-smoke seals, to prevent smoke from spreading rapidly along the corridor and making evacuation difficult.

  1. Double swing fire doors in luxury hotel corridors

In luxury hotels, double-leaf fire doors (EI 60 or EI 120) can be installed in the widest corridors, ensuring both fire safety and elegant aesthetics.

  1. Compartmentalized corridors near the kitchens

Corridors adjacent to kitchens are separated by fire doors of the class required by the design, to prevent any fires in the kitchens from spreading rapidly into residential areas.

  1. Corridor separation with fire doors in historic buildings

In hotels located in historic buildings, custom-made fire doors can be installed in the corridors, respecting the aesthetics of the building but still ensuring fire compartmentation.

  1. Fire doors in the corridors leading to the suites

The access doors to the suites follow the same rules as the room doors (under the Ministerial Decree (D.M.) of 9 April 1994, at least RE 30 with self-closing in new buildings), to protect the main corridor and the rooms in the event of a fire.

  1. Fire doors with resistant glass in corridors adjacent to public areas

In corridors bordering public areas, such as restaurants or lobbies, fire doors with fire-resistant glass inserts (EI 60) can be used to maintain visibility and visual continuity, while ensuring safety.

  1. After how many rooms should a corridor be compartmentalized?

The Italian Fire Prevention Code does not provide a fixed rule or a predetermined number of rooms to compartmentalize corridors in hotels. However, the compartmentalization of corridors depends on various factors such as:

- Compartment surface area: The Code establishes a maximum limit to the fire compartment surface area, which depends on the floor level and the risk profile: for hotels (profile Ciii) the values are given in the table in Chapter S.3.

- Distance from escape routes: Corridors must ensure that escape routes are not too long, so that occupants can evacuate quickly. The maximum length of the escape route is set by the chosen technical rule, and it can increase if automatic extinguishing systems such as sprinklers are present.

- Fire resistance class: The horizontal compartmentalization of corridors, especially on floors with guest rooms, is achieved with fire doors of the class required by the design, which close the corridor sections to prevent the spread of fire and smoke.

In general, compartmentalization must be designed considering the building configuration, crowding, height and length of escape routes, with the aim of ensuring safe escape for occupants and protection of escape routes.

Conclusions

Fire compartmentation is a fundamental strategy to ensure the safety of guests and staff in hotels. Through the correct division of spaces into fire-resistant compartments and the separation of escape routes, it is possible to limit the spread of flames and smoke, facilitating safe evacuation and minimizing structural damage.

The choice of fire doors and other fire-resistant elements is crucial to comply with current regulations and ensure that each compartment offers the necessary protection in the event of a fire. The most effective solutions involve the use of certified doors, designed to meet the requirements of the Fire Prevention Code.

If you are looking for certified fire doors for hotels, visit our fire door collection: EI 60 wooden doors for guest rooms and metal REI doors for technical rooms. To find out when a REI door is mandatory, read our guide to REI doors; for classes and prices, see the guide on how much a REI fire door costs.

The information provided in this article is general in nature and does not constitute professional advice. Each project must be reviewed and approved by certified fire safety and regulatory compliance experts.

Porte Italiane declines all responsibility for any errors, omissions or consequences arising from the use of the information contained in this article without due technical advice.

Icona WhatsApp